CBM / DESIGN ZONE

Soil measurements (Wenner method)

Enter the meter readings, compare apparent resistivity and carry the result into the calculation.

Check which meter you have. This calculator is only for converting readings from meters that do not measure soil resistivity automatically. If your meter measures resistivity, you do not need this calculator.

MEASUREMENT SERIES

Meter readings

Example data
  1. Enter the meter readings: for each measurement, give the electrode spacing a and the resistance R read from the meter. The white fields are for your input.
  2. We calculate the resistivity ρₐ in the last column. Click “Measurement 1”, “Measurement 2”… to view the electrode layout and the result of that measurement.
MeasurementElectrode spacing a [m]enterMeter reading R [Ω]enterρₐ [Ω·m]resultRemove
100.53
94.25
80.42
70.37
APPARENT RESISTIVITYρₐ = 2π · a · R

Model of electrodes with negligible depth relative to the spacing. Reading R is the resistance measured with the four-electrode array.

Four-electrode array

Wenner
4P METERC1a = 1.0 mP1a = 1.0 mP2a = 1.0 mC2
C1 / C2: currentP1 / P2: voltageNot to scale
SELECTED MEASUREMENT / ρₐ
100.5 Ω·m
Result from example data
Spacing of adjacent electrodes1.0 mArray length 3a3.0 m

From measurement to calculation

The selected value is taken as an assumption of uniform soil. Compare the results of different measurements before choosing a design value. You can carry the result into the ring earth plan (step 2) to calculate the ring earth resistance, or straight into the earthing calculator (step 3).

MEASUREMENT COMPARISON

How does apparent resistivity change?

ρₐ [Ω·m]0.025.150.375.4100.51.02.04.08.0Spacing a [m]

Compare rows by selecting “Measurement 1”, “Measurement 2”… in the table. The chart is not a cross-section of soil layers; a larger spacing measures a larger volume of soil.

Method, scope and sources

ρₐ = 2πaR, a in metres, R in ohms. If electrode depth is not negligible, a geometric correction is needed, which this model does not include. The measurement requires equal spacing of the four electrodes. Results from different spacings and directions are not averaged automatically.

Megger: measurement method · EPA: apparent resistivity and interpretation

NEXT STEP 2 OF 3

Ring earth calculator

The result of the selected measurement (Measurement 1, ρₐ = 100.5 Ω·m) will be carried into the ring earth plan as the soil resistivity, and on to the earthing calculator.

Go to step 2